Oklahoma Administrative Code (Last Updated: March 11, 2021) |
TITLE 165. Corporation Commission |
Chapter 25. Underground Storage Tanks |
Subchapter 8. Special Requirements for Underground Storage Tank Systems Utilized by Marinas |
Part 11. MISCELLANEOUS SAFETY REQUIREMENTS |
SECTION 165:25-8-36. Fire extinguishers
Latest version.
- (b) A minimum of three extinguishers must be located at the fuel dock, and one or more must be located within 50 feet (50' or 15 meters) of each pump, dispenser, and underground fill pipe opening.(c) Piers that extend more than 500 feet (500' or) one hundred fifty-two meters (152 m) in travel distance from shore must have a Class III standpipe installed in accordance with NFPA 14, Standard for the Installation of Standpipe and Hose Systems.(d) There must be a knife readily accessible at the fuel dock for quickly cutting mooring lines in an emergency and a push pole for shoving away a boat.