Oklahoma Administrative Code (Last Updated: March 11, 2021) |
TITLE 165. Corporation Commission |
Chapter 26. Aboveground Storage Tanks |
Subchapter 1. General Provisions |
Part 7. NOTIFICATION AND REPORTING REQUIREMENTS |
SECTION 165:26-1-48. Tank and line tightness testing
Latest version.
- (a) Tank and line tightness test results in which any part of the tank system tested does not pass must be reported to PSTD within twenty-four (24) hours by the owner, operator, their employees or agents, and also independently by the person or company performing the test. Complete test results must be submitted within seven (7) days of the testing.(b) Hydrostatic line tightness tests must be conducted by a certified tester, if applicable, in accordance with manufacturer's instructions, and reported on the required PSTD form.(c) The tester performing line and leak detector tests must certify that the line leak detector is installed properly.(d) All personnel performing tank and line testing must have the required education, experience, applicable certification, knowledge and competence to correctly perform testing services in accordance with the testing equipment, manufacturer certification and applicable industry standards or codes.(e) Tank and line tightness testing must be scheduled by submitting the PSTD scheduling form and PSTD staff may be present.