Oklahoma Administrative Code (Last Updated: March 11, 2021) |
TITLE 165. Corporation Commission |
Chapter 26. Aboveground Storage Tanks |
Subchapter 2. General Requirements for Aboveground Storage Tank Systems |
Part 1. DESIGN AND INSTALLATION |
SECTION 165:26-2-4. Distance to be kept around tanks
Latest version.
- (1) 50 ft (15 meters) from the nearest important building as defined by this Chapter;(2) 50 ft (15 meters) from any fuel dispenser;(3) 50 ft (15 meters) from the nearest side of a public way; and(4) 100 ft (30 meters) from any property line that is or might be built upon, including the opposite side of a public way.(b) The distances as set forth in (a) of this may be reduced by 50 percent if the tanks are fire-resistant. The distances as set forth in (a) may be further reduced if the tanks are a fire-protected tank or tanks in vaults as per NFPA 30A-4.3.2.4.(c) A variance may be granted for pre-existing facilities where compliance would be difficult and expensive and the current distances between tanks, property lines or dispensers pose no serious threat to people or property.