Oklahoma Administrative Code (Last Updated: March 11, 2021) |
TITLE 165. Corporation Commission |
Chapter 35. Electric Utility Rules |
Subchapter 17. Frequency, Voltage, and Equipment Servicing Requirements |
SECTION 165:35-17-2. Voltage limits
Latest version.
- (a) Secondary voltages. The voltage at the utility's point of delivery, as installed for each consumer, shall be maintained within the limits specified in (1) through (4) of this subsection. If a utility adopts any standard voltage not included in the table in (4) of this subsection, it shall advise the Commission that the Commission may establish appropriate voltage limits. Where three-phase service is provided, the utility shall exercise reasonable care to assure that the phase voltages are balanced. The preferred and tolerable voltage ranges conform to the current version of ANSI Standard C84.1, or equivalent ANSI standard as later amended.(1) Preferred secondary voltages. The secondary voltage described above shall normally be maintained within the preferred range specified in the table in (4) of this subsection.(2) Tolerable secondary voltage. The secondary voltage described above will be permitted in the tolerable range specified in the table in (4) of this subsection under abnormal conditions if it is limited in frequency of occurrence and duration, providing that measures are initiated within a reasonable period of time to bring the voltage within the preferred range.(3) Emergency secondary voltages. Voltages outside the limits specified in (4) of this subsection may infrequently occur due to:(A) Addition of significant loads without proper notice to the utility.(B) Adverse action of the elements.(C) Failure of principal supply line or equipment necessitating use of alternate routes.(D) Temporary separation of part of the system from the main system.(E) Causes beyond the control of the utility.(4) Table.PREFERRED VOLTAGETOLERABLE VOLTAGENORMALRANGERANGEVOLTAGEMINIMUMMAXIMUMMINIMUMMAXIMUM120114126110208Y/120197Y/114218Y/126191Y/110220Y/127240/120228/114252/126220/110254/127208197218191220416Y/240395Y/228436Y/252381Y/220440Y/254480/240456/228504/252440/220508/254460Y/265437Y/252483Y/279422Y/244487Y/281480Y/277456Y/263504/Y291440Y/254508Y/293440418462403466480456504440508832Y/480790Y/456873Y/504762Y/440880Y/508600570630550655(b) Primary voltages. The following limits shall apply where the utility supplies service at primary voltage.(1) Industrial consumers. For services rendered principally for industrial or power purposes, the voltage shall not exceed ten percent (10%) above or ten percent (10%) below the nominal voltage of the low side of the transformer.(2) Special contract extension. The limitations in (1) of this subsection do not apply to special contracts in which the consumer specifically agrees to accept service with a different voltage regulation.