Oklahoma Administrative Code (Last Updated: March 11, 2021) |
TITLE 252. Department of Environmental Quality |
Chapter 626. Public Water Supply Construction Standards |
Subchapter 7. Source Development |
SECTION 252:626-7-6. Raw water supply conduit
Latest version.
- (b) Design supply conduits for the following:(1) carrying capacity must meet the ultimate design capacity of the treatment facilities or ultimate maximum daily demand of the community,(2) maximum present and future pressures and water hammer,(3) hydraulic grade, traffic loads, and laying conditions,(4) expansion and contraction, anchorage at bends, and joints,(5) blow-off valves and line valves to isolate line sections, and(6) air inlet and release valves or towers to release air on filling or draining.(c) Flush raw water lines to remove debris before being placed into service.(d) Construct lines conducting water from impoundments or streams of watertight material sized to provide a velocity of 3 B 4 ft/s. The conduit must be capable of drawing water from the source when it is at its lowest elevation at a rate equal to the maximum demand of the pumps.