Oklahoma Administrative Code (Last Updated: March 11, 2021) |
TITLE 310. Oklahoma State Department of Health |
Chapter 667. Hospital Standards |
Subchapter 47. Submittal Requirements |
SECTION 310:667-47-9. Space occupied by other entities
Latest version.
- (a) Areas within a licensed hospital facility that are leased to, or occupied by, a separate entity and comply with Health Care Occupancy requirements as specified by NFPA 101, 2000 edition, shall be separated from the licensed hospital by demising partitions that are rated not less than one (1) hour fire resistance. Lease areas that do not comply with Health care Occupancy requirements as specified by NFPA 101, 2000 edition, shall be separated from the licensed hospital by demising partitions that are rated not less than two (2) hour fire resistance.(b) Lease areas shall have signage that clearly identifies tenant areas from hospial areas.(c) The lease between the hospital and the tenant entity shall require that the tenant area shall be:(1) Maintained to comply with NFPA 101 for Health care Occupancies;(2) Included in the hospital's sprinkler systems, fire alarm systems, and fire drills; and(3) Accessible to representatives of the Department to determine compliance with these standards.(d) A copy of the executed lease agreement shall be submitted to the Department for review as part of the plan approval application process and a current copy shall be available for review by Department staff upon request.