SECTION 748:20-1-9. IBC® 2015 Chapter 4 Special Detailed Requirements Based on Use and Occupancy  


Latest version.
  •   Chapter 4 of the IBC® 2015 is adopted with the following modifications:
    (1)   Section 406.7.2.1 Canopies used to support gaseous hydrogen systems. This section has been modified by deleting the word "hydrogen" in the heading and in the third requirement; and by adding the wording "lighter-than-air" to the section header to make the section applicable to all lighter-than-air fuels. This section has been modified to read: 406.7.2.1 Canopies used to support lighter-than-air gaseous systems. Canopies that are used to shelter dispensing operations where flammable compressed gases are located on the roof of the canopy shall be in accordance with the following:
    (A)   The canopy shall meet or exceed Type I construction requirements.
    (B)   Operations located under canopies shall be limited to refueling only.
    (C)   The canopy shall be constructed in a manner that prevents the accumulation of gas.
    (2)   Section 406.7.2.2. Canopies sheltering units and devices that dispense lighter-than-air gas. This section has been added to require all canopies to be designed to prevent the accumulation or entrapment of ignitable vapors under canopies when dispensing lighter-than-air gas or all electrical equipment installed beneath the canopy is required to be suitable for Class I, Division 2 hazardous (classified) locations. This section has been added to read: 406.7.2.2 Canopies sheltering units and devices that dispense lighter-than-air gas. Where CNG, LNG, or Hydrogen motor fuel dispensing devices are installed beneath a canopy, the canopy shall be designed to prevent the accumulation or entrapment of ignitable vapors, including provisions for natural or mechanical ventilation means, or all electrical equipment installed beneath the canopy or within the enclosure shall be suitable for Class I, Division 2 hazardous (classified) locations. Tank vents that are installed within or attached to the canopy shall extend a minimum of 5 feet (1524 mm) above the highest projection of the canopy. Compression and storage equipment located on the top of the canopy shall be in accordance with current State of Oklahoma adopted International Fire Code®, Section 2309.
    (3)   Section 419.1 General. This section has been modified to add a new exception to allow Group B, M, and F occupancies located in a detached dwelling unit to be constructed in accordance with the IRC® if they comply with the limitations in Section 419.1.1. This section has been modified to read: 419.1 General. A live/work unit shall comply with Sections 419.1 through 419.9. Exceptions:
    (A)   Dwelling or sleeping units that include an office that is less than 10 percent of the area of the dwelling unit are permitted to be classified as dwelling units with accessory occupancies in accordance with Section 508.2.
    (B)   Group B, M, and F occupancies that are located in a detached dwelling unit complying with the limitations of Section 419.1.1 shall be permitted to be constructed in accordance with the IRC®.
    (4)   Section 419.1.1 Limitations. This section has been modified to limit the nonresidential portion of the live/work unit to not greater than 2,500 square feet (232 square meters). This section has been modified to read: 419.1.1 Limitations. The following shall apply to all live/work areas:
    (A)   The nonresidential portion of the live/work unit is permitted to be not greater than 2,500 square feet (232 square meters) in area;
    (B)   The nonresidential area is permitted to be not more than 50 percent of the area of each live/work unit;
    (C)   The nonresidential area function shall be limited to the first or main floor only of the live/work unit; and
    (D)   Not more than five nonresidential workers or employees are allowed to occupy the nonresidential area at any one time.
    (5)   Section 423.1.1 Scope. This section has been modified to include above and below ground storm shelters and limit the use of the term storm shelter to those structures constructed according to this section. This section has been modified to read: 423.1.1 Scope. This section applies to the construction of above or below ground storm shelters constructed as separate detached buildings, or rooms within buildings, structures, or portions thereof for the purpose of providing safe refuge from storms that produce high winds, such as tornados and hurricanes. Any room or structure, as may be used as a place of refuge during a severe wind storm event, shall not be defined as a storm shelter unless specifically designed to the requirements as listed in Section 423.
    (6)   Section 423.3 Critical emergency operations. This section, including the exception, has been moved to the newly created Appendix N, entitled "Supplemental Storm Shelter Requirements" and is not adopted as a minimum standard for residential or commercial construction within the State of Oklahoma. This section has been renumbered in Appendix N to become N102. The section number 423.3 itself, will stay as part of this code for numbering alignment but will not have any requirements attached to it.
    (7)   Section 423.4 Group E occupancies. This section, including exceptions, has been moved to the newly created Appendix N, entitled "Supplemental Storm Shelter Requirements" and is not adopted as a minimum standard for residential or commercial construction within the State of Oklahoma. The section has been renumbered in Appendix N to become N103. The section number 423.4 itself, will stay as part of this code for numbering alignment but will not have any requirements attached to it.
    (8)   Section 423.5 Required. This section has been added to specify the requirements when storm shelters are provided. This section has been added to read: 423.5 Required. Where storm shelters are provided, they shall be provided in compliance with ICC 500® except as required by Sections 423.5.1 through 423.5.11.
    (9)   Section 423.5.1 Storm shelter documents. This section has been added to require the construction documents prepared for the storm shelter to be maintained and protected within the storm shelter by the owner or owner's authorized agent. This section has been added to read: 423.5.1 Storm shelter documents. The construction documents which were prepared for the construction of the storm shelter, shall be maintained and protected within the storm shelter by the owner or owner's authorized agent.
    (10)   Section 423.5.2 Signage. This section has been added to clarify that all signs for a storm shelter, as outlined in ICC 500® Sections 108, 504.1, 504.1.1, and 504.1.2, comply with the applicable signage requirements of ICC A117.1®. This section has been added to read: 423.5.2 Signage. All signs, as outlined in ICC 500® Sections 108, 504.1, 504.1.1 and 504.1.2 shall comply with the applicable requirements of ICC A117.1®.
    (11)   Section 423.5.2.1 Entrance signage. This section has been added to clarify entrance signage as required by ICC 500® Section 504.1.1 is not required for the storm shelter when the storm shelter can be accessed from within the host building and is only open to the occupants of the host building. This section has been added to read: 423.5.2.1 Entrance signage. Entrance signage, as outlined in ICC 500® Section 504.1.1 shall not be required at exterior entrances where the shelter can be accessed from within a host building and is only open to the occupants of the host building.
    (12)   Section 423.5.3 Roof live load reduction for shelters. This section has been added to clarify roof live loads may not be reduced as allowed in Section 1607.12.2.1 (Equation 16-26) if the roof live load is stipulated under ICC 500® Section 303.2. This section has been added to read: 423.5.3 Roof live load reduction for shelters. Roof live load reduction in Section 1607.12.2.1 (Equation 16-26) shall not be allowed for roof live loads stipulated under ICC 500® Section 303.2.
    (13)   Section 423.5.4 Design wind speed. This section has been added to modify the requirements of ICC 500® Section 304.2 to clarify the minimum design wind speed for all storm shelters in the State of Oklahoma shall be set at 250 miles per hour. This section has been added to read: 423.5.4 Design wind speed. For storm shelters, the minimum design wind speed for the entire State of Oklahoma shall be 250 miles per hour.
    (14)   Section 423.5.5 Usable storm shelter floor area. This section has been added to modify the requirements of ICC 500® Section 501.1.2 to clarify when calculating the maximum usable floor area of a shelter, the areas within a privacy enclosure for sanitary facilities shall not be included. This section has been added to read: 423.5.5 Usable storm shelter floor area. The usable storm shelter floor area shall be determined by ICC 500® Section 501.1.2.1 or 501.1.2.2. Exception: Areas within privacy enclosures for sanitary facilities shall not be included in the usable floor area calculations.
    (15)   Section 423.5.6 Door operation. This section has been added to modify the requirements of ICC 500® Section 501.5 to specify means of egress doors shall be operable from the inside of the storm shelter without the use of keys or special knowledge or effort. This section has been added to read: 423.5.6 Door operation. Means of egress doors shall be operable from the inside without the use of keys or special knowledge or effort.
    (16)   Section 423.5.6.1 Additional doors and shutters operation. This section has been added to clarify doors and shutters designed to protect windows and other unprotected openings not required as a means of egress in storm shelters shall be operable from the inside without the use of keys or special relocatable tools. This section has been added to read: 423.5.6.1 Additional doors and shutters operation. Doors and shutters designed to protect windows or other unprotected openings not in a required means of egress in storm shelters shall be operable from the inside without the use of keys or special relocatable tools.
    (17)   423.5.7 Height of storm shelter. This section has been added to clarify how to determine the location of the natural ventilation openings in storm shelters in accordance with ICC 500® Section 702.1.1.1, by providing a definition for the height of the storm shelter to be calculated by average of the vertical dimensions from the floor elevation to the bottom of the storm shelter deck or to the underside of a hard ceiling within the storm shelter. This section has been added to read: 423.5.7 Height of storm shelter. When determining the location of natural ventilation in accordance with ICC 500® Section 702.1.1.1, the height of the storm shelter shall be defined as an average of the vertical dimensions from the floor elevation to the bottom of the storm shelter deck or to the underside of a hard ceiling within the storm shelter.
    (18)   Section 423.5.8 Additional facilities for storm shelters. This section has been added to modify the requirements of ICC 500® Section 702.2.2 to clarify when the required number of sanitation facilities for the storm shelter exceeds the number of required facilities provided for the normal occupancy of space, additional facilities may be temporary toilets, chemical toilets or other approved means and must have privacy enclosures with minimum clear inside dimensions of 5 feet by 5 feet (1524 mm by 1524 mm). This section has been added to read: 423.5.8 Additional facilities for storm shelters. Where the required number of sanitation facilities for the storm shelter exceeds the number of facilities provided for the normal occupancy of the space, the additional facilities shall be permitted to be temporary sanitary fixtures, chemical toilets, or other means approved by the authority having jurisdiction. Temporary toilets, chemical toilets, or other approved means shall have temporary or permanent privacy enclosures such as fabric, portable screens, or other means approved by the authority having jurisdiction. Privacy enclosures shall have minimum clear inside dimensions of 5 feet by 5 feet (1524 mm by 1524 mm).
    (19)   Section 423.5.9 Sanitary facilities support systems. This section has been added to modify the requirements of ICC 500® Section 702.2.3 to clarify the support systems discussed in the section are for temporary sanitation facilities. This section has been added to read: 423.5.9. Sanitary facilities support systems. Support systems for the temporary sanitation facilities (e.g. bladders, storage tanks or vessels, etc.) shall be capable of supplying water and containing waste for the design capacity of the tornado shelter.
    (20)   Section 423.5.10 Conversion of plumbing systems. This section has been added to omit ICC 500® Section 702.2.4 from the minimum requirements of the code. This section has been added to read: 423.5.10 Conversion of plumbing systems. ICC 500® Section 702.2.4 is omitted.
    (21)   Section 423.5.11 First aid kit. This section has been added to modify the requirements of ICC 500® Section 702.4 to specify that first aid kits for community shelters shall be required to be ANSI rated for the number of occupants in the shelter. This section has been added to read: 423.5.11 First aid kit. An ANSI compliant first aid kit rated for the number of storm shelter occupants, as listed in the construction documents, shall be supplied in all tornado shelters.
[Source: Added at 29 Ok Reg 1646, eff 11-1-12; Amended at 32 Ok Reg 2270, eff 11-1-15; Amended at 34 Ok Reg 2107, eff 9-15-17; Amended at 35 Ok Reg 2137, eff 9-17-18]