SECTION 748:20-15-16.1. IPC® 2015 Chapter 13 Nonpotable Water Systems  


Latest version.
  •   Chapter 13 of the IPC® is adopted with the following modification: Section 1301.9.6 Overflow. This section has been modified to require the section to apply to any walkway not just those on roofs. This section has been modified to read: 1301.9.6 Overflow. The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in Table 606.5.4. The overflow pipe shall be protected from insects or vermin and shall discharge in a manner consistent with storm water runoff requirements of the jurisdiction. The overflow pipe shall discharge at a sufficient distance from the tank to avoid damaging the tank foundation or the adjacent property. Drainage from overflow pipes shall be directed to prevent freezing on walkways. The overflow drain shall not be equipped with a shutoff valve. A cleanout shall be provided on each overflow pipe in accordance with Section 708.