SECTION 748:20-3-13.5. IFC® 2015 Chapter 61 Liquefied Petroleum Gases  


Latest version.
  •   Chapter 61 of the IFC® 2015 is adopted with the following modifications:
    (1)   Section 6106.1 Attendants. This section has been modified to provide an exception to the requirement for a qualified attendant if the motor fuel-dispensing equipment meets the guidelines of NFPA® 58 for a "Low emission transfer." This section has been modified to read: 6106.1 Attendants. Dispensing of LP-gas shall beperformed by a qualified attendant. Exception: When the dispensing equipment meets theguidelines of NFPA® 58 for "Low emission transfer" an attendant is not required.
    (2)   Section 6106.2 Overfilling. This section has been modified to include an overfilling prevention device on the container as one of the ways to measure the volume in the container. This section has been modified to read: 6106.2 Overfilling. LP-gas containers shall not be filled or maintained with LP-gas in excess of either the volume determined using the fixed liquid-level gauge installed in accordance with the manufacturer's specifications and in accordance with Section 5.7.5 of NFPA® 58, the volume determined by the overfilling prevention device installed on the container, or the weight determined by the required percentage of water capacity marked on the container. Portable LP-gas containers shall not be refilled unless equipped with an overfilling prevention device (OPD) where required by Section 5.7.3 of NFPA®58.
[Source: Added at 34 Ok Reg 2107, eff 9-15-17]