SECTION 748:20-3-8. IFC® 2015 Chapter 5 Fire Service Features  


Latest version.
  •   Chapter 5 of the IFC® 2015 is adopted with the following modification: Section 508.1.3 Size has been modified to include an exception to make the fire command center smaller when approved by the fire code official. This section has been modified to read: 508.1.3 Size. The fire command center shall be a minimum of 200 square feet (19 square meters) in area with a minimum dimension of 10 feet (3048 mm). Exception: When approved by the fire code official the fire command center can be reduced in size to not less than a minimum of 96 square feet (9 square meters) with a minimum dimension of 8 feet (2438 mm).
[Source: Added at 29 Ok Reg 1646, eff 11-1-12; Amended at 32 Ok Reg 2270, eff 11-1-15]