SECTION 748:20-9-6.2. NEC® 2014 Chapter 2 Wiring and Protection  


Latest version.
  •   Chapter 2 is adopted with the following modification: Section 210.19 (A)(4) Other Loads. This section has been modified to provide adequate loads per circuits. This section has been modified to read: Branch-circuit conductors that supply loads other than those specified in 210.2 and other than cooking appliances as covered in 210.19 (A)(3) shall have an ampacity sufficient for the loads served and shall not be smaller than 14 AWG. 20 ampere general-purpose branch circuits for dwellings shall supply a maximum of 10 outlets. 15 ampere general-purpose branch circuits for dwellings shall supply a maximum of 8 outlets. 20 ampere general-purpose branch circuits for other than dwellings shall supply a maximum of 8 outlets.
[Source: Added at 32 Ok Reg 2270, eff 11-1-15]