SECTION 252:515-13-33. Drainage and protective layer  


Latest version.
  • (a)   Design standards. The drainage and protective layer shall consist of a minimum of 24 inches of material that will maintain a liquid head of less than or equal to 12 inches above, and protect, the underlying FML.
    (b)   Geonet. If a geonet is used:
    (1)   the hydraulic conductivity of a geonet shall be 1 x 10-1 cm/sec or greater;
    (2)   the geonet shall be placed on the bottom and side slopes of the disposal cell, directly on top of the geomembrane;
    (3)   geotextile fabric shall be placed directly on the geonet; and
    (4)   the geonet shall be tied into a removal pipe system designed to meet the standards for collection pipes.
[Source: Added at 20 Ok Reg 1151, eff 6-1-03]